{"category":"engineering","options":"['I_g= 25 amp, I_m= 30 amp, I of main generator = 490 amp', 'I_g= 15 amp, I_m= 20 amp, I of main generator = 465 amp', 'I_g= 24 amp, I_m= 31 amp, I of main generator = 481 amp', 'I_g= 20 amp, I_m= 25 amp, I of main generator = 480 amp', 'I_g= 18 amp, I_m= 32 amp, I of main generator = 468 amp', 'I_g= 19.5 amp, I_m= 30.5 amp, I of main generator = 469.5 amp', 'I_g= 22.5 amp, I_m= 27.5 amp, I of main generator = 475 amp', 'I_g= 23 amp, I_m= 26 amp, I of main generator = 476 amp', 'I_g= 17 amp, I_m= 33 amp, I of main generator = 467 amp', 'I_g= 21.26 amp, I_m= 28.74 amp, I of main generator = 478.74 amp']","question":"A 125/250-volt three-wire system has a load on the positive side of 500 amp, on the negative side of 450 amp, the neutral current therefore being 50 amp. If each machine of the balancer set has an efficiency of 86 percent, calculate the current for each of these machines and for the main generator.","src":"stemez-ElectricalMachines"}