A 10kVA distribution transformer has a 240V secondary winding. The equivalent internal resistance of this transformer, referred to that winding, is 0.048\Omega. The core lossof this transformer is 75W. At whatkVAload will this transformeroperate at maximum efficiency?

category

engineering

options

  1. 110% of rated load
  2. 90% of rated load
  3. 100% of rated load
  4. 95% of rated load
  5. 50% of rated load
  6. 105% of rated load
  7. 85% of rated load
  8. 70% of rated load
  9. 60% of rated load
  10. 80% of rated load