question

An open-circuit test on a 150-kVa 2400/240-V 60-Hz transformeryielded the following data, corrected for instrumentlosses: Volts Amperes Watts 240 16.75 580 The following data were obtained in a short-circuit test of the transformer, with its low-voltage winding short-circuited. Volts Amperes Watts 63.0 62.5 1660 Calculate the efficiency of the transformer (a) at rated load 0.80 power factor and (b) at one-half rated load 0.60 power factor.

category

engineering

options

  1. 0.9940, 0.9650
  2. 0.9882, 0.9600
  3. 0.9650, 0.9900
  4. 0.9817, 0.9784
  5. 0.9765, 0.9836
  6. 0.9720, 0.9805
  7. 0.9800, 0.9750
  8. 0.9901, 0.9735
  9. 0.9756, 0.9821
  10. 0.9850, 0.9700