MMLU-Pro / 11922 / A 2,000-kva 2,300-volt three-phase alternator operates at ratedkilovolt-amperes…

Problem

Answer published by the source. Consult the official source to check your work against its answer.

question

A 2,000-kva 2,300-volt three-phase alternator operates at ratedkilovolt-amperes at a power factor of 0.85. The d-c armature-windingresistance at 75°C between terminals is 0.08 ohm.The field takes 72ampat 125 volts from exciter equipment. Friction andwindageloss is 18.8kw, iron losses are37.6kw, and stray-load losses are 2.2kw. Calculate the efficiencyof the alternator. (Assume that the effective armature-windingresistance is 1.3 times the d-c value.)

category

engineering

options

  1. 98.3
  2. 90.5
  3. 92.7
  4. 88.5
  5. 94.1
  6. 85.2
  7. 93.6
  8. 91.2
  9. 87.9
  10. 89.4

src

stemez-ElectricalMachines