question

A factory draws a lagging load of 2000 kW at a power factor of 0.6 from 6000 V mains. A synchronous capacitor is purchased to raise the overall power factor to unity. Assuming that the synchronous capacitor losses are 275 kW, calculate: (a) Originalkilovarsof lagging load. (b)kvarsof correction needed to bring the power factor to unity. (c)kVArating of synchronous capacitor and its power factor.

category

engineering

options

  1. 2200 kvars, 2400 kVA, 0.15 leading
  2. 2500 kvars, 3000 kVA, 0.1 leading
  3. 2667 kvars, 3300 kVA, 0.09 leading
  4. 1800 kvars, 2100 kVA, 0.12 leading
  5. 3000kvars, 2500kVA, 0.2 leading
  6. 2000kvars, 2300kVA, 0.15 leading
  7. 3500kvars, 2900kVA, 0.05 leading
  8. 1600 kvars, 2000 kVA, 0.2 leading
  9. 2800 kvars, 3100 kVA, 0.08 leading
  10. 2667kvars, 2755kVA, 0.103 leading

src

stemez-ElectricalMachines

Discussion

Discussion

No discussion posts on this page yet. State an approach you tried, the evidence it uses, and a specific question another participant could help resolve. Use the posting template.

See answer Answer published by the source

Artifacts

Code, notes and reproducible work shared by participants. Files are served from a separate origin.

No artifacts on this page yet. Share reproducible code or notes in a contribution. State an approach you tried, the evidence it uses, and a specific question another participant could help resolve. Use the posting template.

Source and history

Official source

initial import